Americool Portable Air Conditioners Alarm Codes

11 komentar
Americool Portable Air Conditioners Alarm Codes Model HPC-3000 / HPC-5000 / WPC-7000 / WPC-9000 / WPC-15000

Alarm Display = 1C
Problem = Frost preven on sensor and Abnormal temperature sensor value
Cause = • Indoor heat exchanger temperature too low
• TH3 temperature sensor has a loose or broken connec on
Corrective Action = • Do not use the air conditioner if ambient
temperature is lower than 18°C (64°F)
• Contact a qualified service agent

Alarm Display = P5
Problem = Refrigerant high pressure switch
Cause = • Blocked air fi lter
• Blocked /kinked exhaust duct
• Ambient temperature is too high
Corrective Action = Clean air filter
• Ensure exhaust duct is not blocked / kinked
• Do not use the air conditioner if ambient temperature is higher than 45°C (113°F)

Alarm Display = 51
Problem = Abnormal temperature sensor value
Cause = TH1(Outlet) temperature sensor has a loose or broken connection
Corrective Action = Contact a qualified service agent

Alarm Display = 52
Problem = Abnormal temperature sensor value
Cause =  TH2(Inlet) temperature sensor has a loose or broken connection
Corrective Action = Contact a qualified service agent

Alarm Display = C0
Problem = Compressor overloaded
Cause = • Ambient temperature is too high
• Unstable voltage supply
• Defective compressor
Corrective Action = • Do not use the air conditioner if ambient temperature is higher than 45°C (113°F)
• Contact a qualified service agent
• Replace compressor

Alarm Display = Ft
Problem = Condensate water level alarm
Cause = Condensate tank is full
Corrective Action = • Empty the water tank
• A er installa on of the water tank, press the SPOT/COOL or ROOM/COOL bu on to resume
operation

Alarm Display = FU
Problem = Drain pump alarm
Cause = Drain pump defective or improper hose connection (including kink or blockage)
Corrective Action = • Check the hose connection and hose
• Replace drain pump


Read More ->>

Thursday, August 7, 2014

Daikin Ururu Sarara Error Code

2 komentar
Inverter Pair E-Series

Heat Pump
Indoor Units
FTXR28EV1B
FTXR42EV1B
FTXR50EV1B

Outdoor Units
RXR28EV1B
RXR42EV1B
RXR50EV1B


Code = Basic Failure Diagnosis
Unit = Basic Failure Diagnosis
Description = Air conditioner does not run.

Code = Basic Failure Diagnosis
Unit = Basic Failure Diagnosis
Description = Air conditioner runs but does not get cooling (heating)

Code = Basic Failure Diagnosis
Unit = Basic Failure Diagnosis
Description = When operation starts, safety breaker works.

Code = Basic Failure Diagnosis
Unit = Basic Failure Diagnosis
Description = Air conditioner makes big noise and vibration.

Code = Basic Failure Diagnosis
Unit = Basic Failure Diagnosis
Description = Air does not humidified enough

Code = A1
Unit = Indoor
Description = Indoor unit PCB fault

Code = A5
Unit = Indoor
Description = Peak-cut control or freeze-up protection

Code = A6
Unit = Indoor
Description = Fan motor system fault

Code = AH
Unit = Indoor
Description = Streamer unit fault

Code = C4
Unit = Indoor
Description = Indoor heat exchanger thermistor fault

Code = C7
Unit = Indoor
Description = Front panel open / close fault

Code = C9
Unit = Indoor
Description = Room temperature thermistor fault

Code = CC
Unit = Indoor
Description = Humidity sensor fault

Code = E1
Unit = Outdoor
Description = Outdoor unit PCB fault

Code = E5
Unit = Outdoor
Description = OL activation (compressor overload)

Code = E6
Unit = Outdoor
Description = Compressor lock

Code = E7
Unit = Outdoor
Description = DC fan lock

Code = E8
Unit = Outdoor
Description = Input overcurrent detection

Code = EA
Unit = Outdoor
Description = Four way valve fault

Code = F3
Unit = Outdoor
Description = Discharge pipe temperature control

Code = F6
Unit = Outdoor
Description = High pressure control in cooling

Code = H0
Unit = Outdoor
Description = Compressor sensor system fault

Code = H1
Unit = Humidifying unit
Description = Damper fault

Code = H6
Unit = Outdoor
Description = Position sensor fault

Code = H8
Unit = Outdoor
Description = DC voltage / DC current sensor fault

Code = H9
Unit = Outdoor
Description = Outdoor air thermistor fault

Code = J3
Unit = Outdoor
Description = Discharge pipe thermistor fault

Code = J6
Unit = Outdoor
Description = Outdoor heat exchanger thermistor fault

Code = L3
Unit = Outdoor
Description = Abnormal temperature in electrical box

Code = L4
Unit = Outdoor
Description = Temperature rise in radiation fin

Code = L5
Unit = Outdoor
Description = Output overcurrent

Code = P4
Unit = Outdoor
Description = Radiation fin thermistor fault

Code = P9
Unit = Humidifying unit
Description = Fan motor system fault / fan lock

Code = PA
Unit = Humidifying unit
Description = Heater wire fault

Code = PH
Unit = Humidifying unit
Description = Humidification fan outlet thermistor fault / abnormal heater temperature

Code = U0
Unit = System
Description = Insufficient gas

Code = U2
Unit = System
Description = Over voltage protection (OVP) / low voltage protection (LVP)

Code = U4
Unit = System
Description = Signal transmission error (indoor unit - outdoor unit)

Code = U4
Unit = Outdoor
Description = Outdoor unit PCB fault or communication circuit fault

Code = U7
Unit = System
Description = Signal transmission error on outdoor unit PCB

Code = UA
Unit = System
Description = Incompatible power supply between indoor unit and outdoor unit

Code = UA
Unit = Indoor
Description = Incomplete setting for hose length

Code = -
Unit = System
Description = Lights-out of microcomputer status lamp

Read More ->>

Monday, May 12, 2014

MITSUBISHI CITY MULTI FAULT CODE

35 komentar
FAULT CODE =  403
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Comms fault between boards - check inverter error detail for which 2 boards, check transformer, bus voltage and inter-connecting cables

FAULT CODE = 900
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Lossnay unit in test run

FAULT CODE = 1102
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = High compressor discharge temperature. Discharge temperature has exceeded 110°C or more. Short of refrigerant. Discharge thermistor

FAULT CODE = 1111
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure/temperature fault - check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter

FAULT CODE = 1112
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure/temperature fault - check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter

FAULT CODE = 1113
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure/temperature fault - check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter

FAULT CODE = 1202
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary fault to 1102

FAULT CODE = 1204
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary heat exchanger gas temperature sensor fault - check thermistors 10a and 10b

FAULT CODE = 1205
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH5)

FAULT CODE = 1211
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH2)

FAULT CODE =  1214
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (THHS)

FAULT CODE = 1216
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH7)

FAULT CODE = 1217
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH8)

FAULT CODE = 1219
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH9)

FAULT CODE = 1221
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH6)

FAULT CODE = 1243
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH10)

FAULT CODE = 1301
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure fault (63L operation) low pressure sensor sensing less than 1 bar immediately before starting

FAULT CODE = 1302
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = High pressure fault - check pressure in system for more than 29 bar (R407c) 38 bar (R410A). Check high pressure sensor against gauge pressure

FAULT CODE = 1368
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS1) at BC - compare pressure reading on SW1 on O/C

FAULT CODE = 1370
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS3) at BC - compare pressure reading on SW1 at O/C

FAULT CODE = 1402
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary fault to 1302

FAULT CODE = 1500
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = System overcharge. Abnormal low compressor superheat - discharge thermistor TH4

FAULT CODE = 1501
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = High compressor shell temp - check for shortage of gas, insufficient indoor index running (comms room units)

FAULT CODE = 1505
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Suction pressure abnormal - generated by low pressure sensor detecting a vacuum - check for blockage, closed valve or sensor fault

FAULT CODE = 2500
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Detecting lack of water flow on a water circuit

FAULT CODE = 2502
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = I/C has water level in drip tray, when the unit was running in cooling (temperature sensors - check for open or closed circuit and operation of pump)

FAULT CODE = 2503
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = I/C has water level in drip tray when the unit was running in cooling (float sensor - check for closed circuit on float switch and operation of pump)

FAULT CODE = 2600
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Water leak from humidifier

FAULT CODE = 4100
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Compressor over current protection on Mr Slim with M-net interface - check inverter or compressor

FAULT CODE = 4101
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Compressor over current protection on Mr Slim with M-net interface - check inverter or compressor

FAULT CODE = 4102
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Open phase fault - check power supply and noise filter for loss of phase, check wiring and fuses

FAULT CODE = 4103
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Reverse phase fault - check phase rotation, loss of phase through the noise filter, fuse blown and high pressure switch open at power on

FAULT CODE = 4106
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Transmission power supply fault - check wiring, high current, incorrect voltage on transmission line and/or M-Net board

FAULT CODE = 4108
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Over current protection on DOL compressor - check power supply, contactor and compressor

FAULT CODE = 4115
R22 = x
R407c = x        
R410A = x                                                              
LOSSNAY = -
DESCRIPTION = Power supply abnormal - check power, fuses, connections and PCB

FAULT CODE = 4116
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Fan motor abnormal - check fan motor and board (relates to indoor unit or Lossnay unit)

FAULT CODE = 4124
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Thermal switch (49C) open circuit on Mr Slim on M-Net - reset and check pressures and air flow

FAULT CODE = 4210
R22 = x
R407c  = -
R410A = -
LOSSNAY = -
DESCRIPTION = Compressor over current problem - check inverter balance. Compressor and inverter

FAULT CODE = 4220
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Low inverter board BUS voltage. Less than 289VdcDC is detected. - check mains supply

FAULT CODE = 4225
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Low DC voltage on Vdc on fan inverter - check CNVdc for 300Vdc on diode stack and check mains power supply to outdoor unit

FAULT CODE = 4230
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = High temperature on heat sink on inverter - check for blockages in air duct, failure of INV fan or failure of thermistor

FAULT CODE = 4235
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Fan inverter heat sink overheat protection. Reduced airflow through heat sink. Fan motor problem. THHS thermistor problem.

FAULT CODE = 4240
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Over current protection. If high current is detected for more than 10 minutes - check inverter balance. Reduced airflow through heat sink

FAULT CODE = 4245
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Over current protection. Possible ACCT current sensor fault. Should read 280 ohms between pins 1 & 2 and across pins 3 & 4

FAULT CODE = 4250
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Over current protection. Inverter IPM problem. Compressor lock - check inverter balance

FAULT CODE = 4255
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Inverter cooling fan problem - if high static fan is used then check that SW3-9 is on

FAULT CODE = 4260
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary inverter heat sink overheat protection. Reduced airflow through heat sink. Fan motor problem. THHS thermistor problem.

FAULT CODE = 5101
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address

FAULT CODE = 5102
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address

FAULT CODE = 5103
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address

FAULT CODE = 5104
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address (indoor fault - check SW7-3 is off)

FAULT CODE = 5105
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH5 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5106
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH5 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5107
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH7 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5108
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = TH8 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5109
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = TH9 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5110
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH10 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5111
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH11 open/short circuit, disconnected from board/pipe

FAULT CODE = 5112
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH10 open/short circuit, disconnected from board/pipe

FAULT CODE = 5113
R22 = x
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH open/short circuit, disconnected from board/pipe

FAULT CODE = 5114
R22 = x
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH open/short circuit, disconnected from board/pipe

FAULT CODE = 5115
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH15 open/short circuit, disconnected from board/pipe

FAULT CODE = 5116
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH16 open/short circuit, disconnected from board/pipe

FAULT CODE = 5201
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Pressure sensor fault outdoor unit/BC box - check fault code address/SW1 pressure sensor readings

FAULT CODE = 5202
R22 = x
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS2) in the BC box

FAULT CODE = 5203
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS3) in the BC box

FAULT CODE = 5300
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control UH fault - see Mr Slim fault code list

FAULT CODE = 5301
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Current sensor fault, ACCT or DCCT - check inv. error details

FAULT CODE = 5401
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Temperature sensor fault - check CN30 for humidity sensor

FAULT CODE = 5701
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Loose float switch connector - check switch, check CN4F on indoor unit

FAULT CODE = 6201
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = TB7 transmission line communication error - check for voltage abnormality/short

FAULT CODE = 6202
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Transmission processor hardware error - check for noise/short on M-Net cable

FAULT CODE = 6600
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Repeat address fault - two or more units are assigned the same address - correct the repeated address

FAULT CODE = 6601
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Polarity setting error - no voltage or short circuit on the m-net transmission line

FAULT CODE = 6602
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Hardware error of transmission processor. Noise interference. Polarity problem on TB7

FAULT CODE =
R22 =
R407c
R410A =
LOSSNAY = -
DESCRIPTION =

FAULT CODE = 6603
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Bus circuit busy - check if indoor unit, Lossnay unit or anything else has been wired into TB7, instead of TB3

FAULT CODE = 6607
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Communication issue - no response back from unit whilst system is operational

FAULT CODE = 6608
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Communication error - loss of voltage or noise entering the transmission line

FAULT CODE = 6700
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control communication error - R22 type unit connected onto M-Net circuit comms error

FAULT CODE = 6701
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control communication error - R22 type unit connected onto M-Net circuit comms error

FAULT CODE = 6702
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control duplicate address error - two or more R22 type units connected onto M-Net circuit with the same address

FAULT CODE = 6750
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control communication error - R22 type unit connected onto M-Net circuit comms error

FAULT CODE = 6751
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 R/A thermistor fault (P1)

FAULT CODE = 6752
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 frost protection at I/C (P6)

FAULT CODE = 6753
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Comms fault between O/C and I/C

FAULT CODE = 6754
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P5)

FAULT CODE = 6755
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P5)

FAULT CODE = 6756
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 frost protection at I/C (P6)

FAULT CODE = 6757
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = System error

FAULT CODE = 6758
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Comms fault between I/C and O/C

FAULT CODE = 6761
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 R/A thermistor fault (P1)

FAULT CODE = 6762
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 TH2 fault check resistance (P2)

FAULT CODE = 6763
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 Comms fault between I/C and O/C

FAULT CODE = 6764
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P4)

FAULT CODE = 6765
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P5)

FAULT CODE = 6766
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 frost protection at I/C (P6)

FAULT CODE = 6767
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 comms fault between I/C and O/C

FAULT CODE = 6771
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - high pressure abnormality or low pressure abnormality

FAULT CODE = 6772
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - inner thermostat function, discharge temperature abnormality, shell thermostat function, over current protection

FAULT CODE = 6773
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - radiator plate thermostat function

FAULT CODE = 6774
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - outdoor thermistor abnormality

FAULT CODE = 6775
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - pressure sensor abnormality, indoor/outdoor communication error

FAULT CODE = 6776
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - over current shut-off

FAULT CODE = 6777
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - system error

FAULT CODE = 6778
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - normal

FAULT CODE = 6779
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - refrigerant overcharge, abnormal voltage, abnormal CT sensor

FAULT CODE = 6830
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Comms fault between I/C and R/C check connections to MA R/C and check for 12Vdc check R/C not set sub controller

FAULT CODE = 6831
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA R/C communication fault - check connections on TB15 or that the controller was removed while the I/C was powered

FAULT CODE = 6832
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA controller comms fault - check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings

FAULT CODE = 6833
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA controller comms fault check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings

FAULT CODE = 6834
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA Controller comms fault - check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings

FAULT CODE = 6840
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control E6/E8 fault - see Mr Slim fault code list

FAULT CODE = 6841
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control E7/E9 fault - see Mr Slim fault code list

FAULT CODE = 6844
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control EA fault - see Mr Slim fault code list

FAULT CODE = 6845
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control Eb fault - see Mr Slim fault code list

FAULT CODE = 6846
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control EC fault - see Mr Slim fault code list

FAULT CODE = 7100
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Over capacity - (R2 150% index exceeded) (Y 130% index exceeded)

FAULT CODE = 7101
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Capacity setting error - SW2 set wrong on indoors, SW5 on YHMA outdoor, (SW3-10 on older kit)

FAULT CODE = 7102
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Error in number of connected units - loss of M-Net voltage (short or break), no power to BC, wrong SW5 setting on box, wrong box type

FAULT CODE = 7105
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Address setting error - OC or BC addressed wrong

FAULT CODE = 7106
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Attribute setting error - SW3-1 setting on a GUF

FAULT CODE = 7107
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Port setting error - check if too much capacity on a single port, wiring SW2 setting, wrong SW14 setting or wrong units on a box when using multiple boxes

FAULT CODE = 7110
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Check SW5-7 is correctly set

FAULT CODE = 7111
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Remote control sensor fault - SW1 - 1 on and no controllers fitted or faulty remote controller

FAULT CODE = 7113
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Function setting error - wrong SW5 setting or wrong resistors fitted on YHM-A

FAULT CODE = 7117
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Model setting error - SW5 set wrong or wrong resistors in

FAULT CODE = 7130
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Incompatible equipment on M-Net - check split with MAC 399 wired onto the TB5 line TB5 line, not the TB7

Read More ->>

Monday, April 14, 2014

TRANE ERROR CODES

27 komentar
Malfunction Display Section
When malfunction or protection occurs in the air coditioner, corresponding code will be displayed on the screen of the indoor unit and the indicator of outdoor unit will blink accordingly as well.
When protection or mal function is eliminated, display will be back to normal.
9, 12 MBH - 60 and 50 Hz (No LED lights on outdoor PCB)
Code = 1
Malfunction = Storage slug
Error Display
Dual 8 display = EE
Led = Heating LED-pause 3s and blink 15 times
Repair Method = Replace indoor main board

Code = 2
Malfunction = Indoor PCB malfunction
Error Display
Dual 8 display = EE
Led = Heating LED-pause 3s and blink 15 times
Repair Method = Replace indoor main board

Code = 3
Malfunction = Anti-freezing protection
Error Display
Dual 8 display = E2
Led = Running LED pause 3s and blink 2 times
Repair Method = Outdoor ambient temperature too low

Code = 4
Malfunction = Overload of system
Error Display
Dual 8 display = H4
Led = Heating LED-pause 3s and blink 4 times
Repair Method = System abnormal, check if the evaporator and codenser is dirty and blocked

Code = 5
Malfunction = No motor of indoor unit feedback
Error Display
Dual 8 display = H6
Led = Running LED-pause 3s and blink 11 times
Repair Method = Is electro motor mounted normally?

Code = 6
Malfunction = Indoor pipe temperature sensor malfunction
Error Display
Dual 8 display = F2
Led = Cooling LED-pause 3s and blink 2 times
Repair Method = Is it loose? Measure the resistant value with universal meter

Code = 7
Malfunction = Internal ambient temperature sensor malfunction
Error Display
Dual 8 display = F1
Led = Cooling LED-pause 3s and blink 1 times
Repair Method = Is it loose? Measure the resistant value with universal meter

Code = 8
Malfunction = Zero passage abnormal
Error Display
Dual 8 display = UF
Led = Heating and cooling LED blink 7 times at the same time
Repair Method = Replace indoor main board

Code = 9
Malfunction = Overload of compressor
Error Display
Dual 8 display = H3
Led = Heating LED-pause 3s and blink 3 times
Repair Method = Inspect connection state of the overload wire

Code = 10
Malfunction = Startup failure
Error Display
Dual 8 display = Lc
Led = Heating LED-pause 3s and blink 11 times
Repair Method = Check if the resistance of compressor to ground is normal, the outdoor main board may be wrong.

Code = 11
Malfunction = No motor of outdoor unit feedback
Error Display
Dual 8 display = UH
Led = Heating and cooling LED blink 8 times at the same time
Repair Method = This malfunction may happen when outdoor DC electromotor is used

Code = 12
Malfunction = Overcurrent protection
Error Display
Dual 8 display = E5
Led = Running LED-pause 3s and blink 5 times
Repair Method = Is electric network variable?

Code = 13
Malfunction = 4-way valve conversion abnormal
Error Display
Dual 8 display = U7
Led = Cooling LED-pause 3s and blink 20 times
Repair Method = Replace 4-way valve

Code = 14
Malfunction = Phase current detection malfunction of compressor
Error Display
Dual 8 display = U1
Led = Heating LED-pause 3s and blink 13 times
Repair Method = Replace outdoor mainboard

Code = 15
Malfunction = Sync failure
Error Display
Dual 8 display = H7
Led = Heating LED-pause 3s and blink 7 times
Repair Method = Check if the resistance of compressor and resistance to ground is normal, if the compressor is normal, the outdoor main board may be wrong

Code = 16
Malfunction = Current diction malfunction of complete unit
Error Display
Dual 8 display = U5
Led = Cooling LED-pause 3s and blink 13 times
Repair Method = Replace outdoor main board

Code = 17
Malfunction = Outdoor ambient temperature sensor malfunction
Error Display
Dual 8 display = F3
Led = Cooling LED-pause 3s and blink 3 times
Repair Method = Is it loose? Measure the resistance value with uiversal meter

Code = 18
Malfunction = Discharge protection of compressor
Error Display
Dual 8 display = E4
Led = Running LED-pause 3s and blink 4 times
Repair Method = Is it loose? Measure the resistance value with uiversal meter

Code = 19
Malfunction = Break-circuit and short-circuit of outdoor discharge temperature sensor
Error Display
Dual 8 display = F5
Led = Cooling LED-pause 3s and blink 5 times
Repair Method = Is it loose? Measure the resistance value with uiversal meter

Code = 20
Malfunction = Break-circuit and short-circuit of outdoor condenser temperature sensor
Error Display
Dual 8 display = F4
Led = Cooling LED-pause 3s and blink 18 times
Repair Method = Is it loose? Measure the resistance value with uiversal meter

Code = 21
Malfunction = Overheat of carbon fin
Error Display
Dual 8 display = P8
Led = Heating LED-pause 3s and blink 19 times
Repair Method = Is outdoor ambient temperature is too high? I radiator mounted correctly?

Code = 22
Malfunction = DC overcurrent
Error Display
Dual 8 display = UU
Led = Heating and cooling LED blink 11 times at the same time
Repair Method =

Code = 23
Malfunction = Temperature sensor malfunction of carbon fin
Error Display
Dual 8 display = P7
Led = Heating LED-pause 3s and blink 18 times
Repair Method = Replace outdoor main board

Code = 24
Malfunction = Lack of Freon or block protection
Error Display
Dual 8 display = F0
Led = Cooling LED-pause 3s and blink 10 times
Repair Method =

Code = 25
Malfunction = DC input voltage is too high
Error Display
Dual 8 display = PH
Led = Cooling LED-pause 3s and blink 11 times
Repair Method = Is voltage of AC power supply normal?

Code = 26
Malfunction = DC input voltage is too low
Error Display
Dual 8 display = PL
Led = Heating LED-pause 3s and blink 21 times
Repair Method = Is voltage of AC power supply normal?

Code = 27
Malfunction = Commuication malfunction
Error Display
Dual 8 display = E6
Led = Runing LED-pause 3s and blink 6 times
Repair Method = Is outdoor connecting wire reliably connected?

Code = 28
Malfunction = Setting error, indoor and outdoor unit abnormal
Error Display
Dual 8 display = UA
Led = Heating and coolig LED blink 12 times at the same time
Repair Method = Outdoor unit is not mached with indoor unit
Remarks 4min after protection stop of compressor, the malfunction is shown in error code.
In other situation, the malfunction will be displayed by press the light button for 6 times within 4s
Read More ->>

Wednesday, April 9, 2014

DuraChill™ Air and Water Cooled 5, 7.5 and 10 HP Chillers

4 komentar
Display, Alarm and Error Messages
When an alarm or error condition is detected, “Ft” appears in the left display and a corresponding code flashes on the right display. Operational limit
parameter alarms will shut down compressor, fan, pump and heaters. Alphabetical codes will also appear on the right display. An audio alarm will also sound.
After taking corrective action, restart unit to clear fault or error.

Code = 02
Description = Low limit temperature alarm
Action required = Alarm – Process fluid temperature has dropped below low limit temperature setting. Increase heat load or decrease “LL” low temperature alarm setting.
Default = 39ºF (4ºC)

Code = 03
Description = High limit temperature alarm
Action required = Alarm – Process fluid temperature has reached high temperature limit setting.
Decrease heat load or increase “HL” high temperature alarm setting.
Default = 95ºF (35ºC)

Code = 04
Description = Over-Temperature Alarm (Select Models Only)
Action required = Alarm – Process fluid temperature is above factory set high temperature cutout.
On air-cooled condenser units the cutout will reset automatically after the temperature of the fluid is lowered. On water-cooled condenser
units the cutout must be manually reset after the temperature of the fluid is lowered. A red button is accessible through the rear panel.
Default = Units without heater option “OTP” jumpered on PCB

Code = 05
Description = Low liquid level alarm (Select Models Only)
Action required = Delayed Alarm – Activated when the liquid level in the reservoir falls below an acceptable level for 30 seconds. On units with the liquid level float switch option. Wired in series with mechanical flow switch – see “07 Low Flow Alarm”
Default = See Fuse Bit Setting 5.4

Code = 07
Description = Low Flow Alarm
Action required = Alarm – Flow rate has dropped below minimum flow rate setting.
Correct cause of low flow rate or decrease “FL” minimum flow rate setting (See “FL” Section 5.4)
Secondary – Mechanical Flow Switch closes with flow (~4 GPM Minimum). If installed in combination with optional water level float
switch they are wired in series and both must be closed, if either opens due to low water level or low flow this alarm or “EFL” Flow Error (See “EFL” below) may be activated.
Default = ~4 GPM Minimum Required for Flow Switch

Code = 08
Description = High Pressure Alarm
Action required = Delayed Alarm – Activated when fluid outlet pressure has exceeded high pressure limit setting for 30 seconds.
Decrease outlet pressure or raise “FP” fluid pressure limit setting.
Default = 100 PSI 689 kPa

Code = 09
Description = Internal software fault
Action required = Fault – Default unit to ºC or ºF, if fault persists replace Control PCB
NOTE: Some parameters will reset to default values – this could activate another fault code if is cleared. Review and return all parameters to usersettings.
Default = N/A

Code = 10
Description = Triac fault
Action required = Fault – Default unit to ºC or ºF, if fault persists replace Control PCB
NOTE: Some parameters will reset to default values – this could activate another fault code if is cleared. Review and return all parameters to user settings.
Default = N/A

Code = 11
Description = Internal RTD probe fault
Action required = Fault – RTD Sensor, check for open or shorted sensor (Reference resistance values 100[ (ohms) @ 0ºC / 138.51[ @ 100ºC If probe tests good, replace control PCB.
Default = N/A
Code = 12
Description = External RTD probe fault
Action required = Fault – RTD Sensor, check for open or shorted sensor (Reference resistance values 100[ (ohms) @ 0ºC / 138.51[ @ 100ºC If probe tests good, replace control PCB.
Default = N/A

Code = 13
Description = Communications fault
Action required = Fault – Default unit to ºC or ºF, if fault persists replace Control PCB
NOTE: Some parameters will reset to default values – this could activate another fault code if is cleared. Review and return all parameters to user settings.
Default = N/A

Code = 14
Description = ADC fault, internal probe
Action required = Fault – Default unit to ºC or ºF, if fault persists replace Control PCB
NOTE: Some parameters will reset to default values – this could activate another fault code if is cleared. Review and return all parameters to user settings.
Default = N/A

Code = 15
Description = ADC fault, external probe
Action required = Fault – Default unit to ºC or ºF, if fault persists replace Control PCB
NOTE: Some parameters will reset to default values – this could activate another fault code if is cleared. Review and return all parameters to user settings.
Default = N/A

Code = 16
Description = Front Panel – High Ambient Temperature Alarm
Action required = Alarm – Maximum ambient temperature limit. Displayed and settable only in ºC.
NOTE: Air-Cooled Chiller’s rated cooling capacity is dependent on an ambient temperature below 104ºF (40ºC) and performance will
decrease as the ambient temperature rises. Continuous operation at ambient temperatures above 104ºF (40ºC) is not recommend for any air or water cooled chiller.
Default = 45ºC

Code = 17
Description = Rear Panel – High Ambient Temperature Alarm (Select Models Only)
Action required = Alarm – Maximum ambient temperature limit. Displayed and settable only in ºC.
NOTE: Air-Cooled Chiller’s rated cooling capacity is dependent on an ambient temperature below 104ºF (40ºC) and performance will
decrease as the ambient temperature rises. Continuous operation at ambient temperatures above 104ºF (40ºC) is not recommend for any air or water cooled chiller.
Default = 45ºC

Code = 18
Description = Ambient Temperature Probe (P3) Fault (Select Models Only)
Action required = Fault – RTD Sensor, check for open or shorted sensor (Reference resistance values 100[ (ohms) @ 0ºC / 138.51[ @ 100ºC If probe tests good, replace control PCB.
Default = N/A

Code = 19
Description = Pump Overload (DAP1) Fault
Action required = Pump – Check continuity across “DAP1” on PCB through NO contacts on overload relay, reset overload relay, and check pump fuses.
Default = N/A

Code = 20
Description = Compressor Overload (DAF2)
Action required = Compressor Pressure Sensors – See Troubleshooting 7.5.
Default = N/A

Code = 21
Description = Fan Overload (DAF1) Fault
Action required = Fan(s) – Check continuity across “DAF1” on PCB through NO contacts on overload relay(s), reset overload relay, check fan(s) fuses. NOTE: On 10 HP Chillers both overload relays NO contacts wired in series with “DAF1”.
Default = N/A

Code = 22
Description = Pump 2 Overload (DAP2) Fault (Select Models Only)
Action required = Pump 2 Option only – Check continuity through NO contacts on overload relay, reset overload relay, check “Pump 2 Fuses”.
Default = “DAP2” jumpered on PCB

The alarms below will be displayed in the right hand display.
Code = EFL
Description = Low fluid level or Low fluid flow
Action required = Warning / Alarm – Audible alarm will sound 5 times, once every 8 seconds. If alarm condition continues the unit will shut down.
- Fluid level too low for units with fluid level float switch.
- Fluid flow too low for units with flow switch (“P0” no pump - no reservoir option).
Default =

Code = EHA
Description = High Ambient Temperature Alarm
Action required = Alarm – The ambient temperature (measured on Control PCB) is higher the high ambient temperature setting.
Lower the ambient temperature or increase the “HA” temperature limit setting.
Default = 45ºC

Code = EHL
Description = High limit temperature alarm
Action required = Alarm – Process fluid temperature has reached high temperature limit setting.
Decrease heat load or increase “HL” high temperature alarm setting.
Default = 95ºF 35ºC

Code = ELL
Description = Low limit temperature alarm
Action required = Alarm – Process fluid temperature has dropped below low limit temperature setting.
Increase heat load or decrease “LL” low temperature alarm setting.
Default = 39ºF 4ºC

Code = LO H2O
Description = No fluid flow and pressure
Action required = Warning – Indicates the chiller did not detect any fluid flow or pressure upon startup. Unit will normally run after 5 minutes – leave chiller with error code displayed for 5 minutes.
Default =

The codes below will be displayed in the right display and indicate display control status.
Code = LLO
Description = Local Lockout
Action required = Normal – Indicates the Local Lockout feature has been enabled.
Prevents settings from accidentally being changed. To enable the local lockout feature “LLO”, press and hold the “Select / Set” knob until “LLO” is displayed (approximately 5 seconds).
Default =

Code = CAN
Description = Cancel Local Lockout
Action required = Normal – Appears when Local Lockout feature has been canceled. To cancel the local lockout feature, press and hold the “Select / Set” knob until “CAn” is displayed (approximately 5 seconds).
Default =

Code = EC
Description = External remote control active
Action required = Normal – Chiller in standby until remotely activated. (Option)
Default =

Automatic Restart from Alarm Mode
This Chiller is equipped with an automatic restart feature to avoid false alarms. If any alarm condition is detected the chiller will turn off, wait 30 seconds and then turn on.
This is to avoid nuisance trips due to temporary flow obstructions, temperature swings or electrical line noise.
Three restart attempts will be made. If the alarm condition continues to exist then an alarm will sound and the chiller will remain off until the problem is corrected.
Read More ->>

CLIMATIC™ 50 - CHILLERS ERROR CODES ALARMS

0 komentar
001 Flow Rate Water Evaporator
011 Electrical Heater(s)
012 High Outlet Water Temperature
013 Low Inlet Water Temperature
022 Low Outlet Water Temperature
023 High Inlet Water Temperature
040 Pump Flow
041 Pump 1
042 Pump 2
070 Clock card
071 BE50
081 Temperature Probe Water Inlet
083 Temperature Probe Outside
085 Temperature Probe Water Outlet
086 Temperature Probe Water Heat Recovery Inlet
087 Temperature Probe Water Heat Recovery Outlet
092 Circuit 1 Condenser fan
093 Circuit 2 Condenser fan
094 Circuit 3 Condenser fan
108 Correction Power factor
111 Circuit 1 Probe High Pressure
112 Circuit 1 Probe Low Pressure
114 Circuit 1 Compressor(s)
115 Circuit 1 High pressure
117 Circuit 1 Low pressure
118 Circuit 1 Risk of Frosting
121 Circuit 2 Probe High Pressure
122 Circuit 2 Probe Low Pressure
124 Circuit 2 Compressor(s)
125 Circuit 2 High pressure
127 Circuit 2 Low pressure
128 Circuit 2 Risk of Frosting
210 Circuit 1 EEV Driver
211 Circuit 1 EEV Low Superheat Temperature
214 Circuit 1 EEV L.O.P
215 Circuit 1 EEV Valve NOT Closed
216 Circuit 1 EEV Probe Low Pressure or Suction Temperature
217 Circuit 1 EEV Motor
219 Circuit 1 EEV Battery
220 Circuit 2 EEV Driver
221 Circuit 2 EEV Low Superheat Temperature
224 Circuit 2 EEV L.O.P
225 Circuit 2 EEV Valve NOT Closed
226 Circuit 2 EEV Probe Low Pressure or Suction Temperature
227 Circuit 2 EEV Motor
228 Circuit 2 EEV E.E.P.R.O.M
Read More ->>
 

| List of fault or error codes air conditioners © 2014. All Rights Reserved | Template Style by My Blogger Tricks .com | Design by Brian Gardner | Back To Top |